Samsung Air conditioner Error Codes
"Code"
Explanation & Check Points
Ch
Compressor Starting Delay - Crankcase heater initiated
"P0"
System down due to high temperature discharge sensor
"P1"
System down due to the high temperature of condenser
"P2"
Sump Comp Down
"P3"
System down due to the lower temperature switch detection
"P4"
System Start down due to reverse phase of the 3 phase
"P5"
System down due to frozen heat exchanger
"P6"
Error of momentary power failure (dissapears when unit is off/on)
"P7"
Compressor down due to protection control of high pressure sensor
"P8"
Compressor down due to protection control of low pressure sensor
"P9"
Problem removing frost
"PA"
Compressor down due to protection control of condensation ratio
"T1"
Error of OUT TEMP sensor (OPEN/SHORT)
"T2"
Error of COND TEMP sensor (Open/short)
"t3"
Error of PWM Discharge TEMP sensor (Open/Short)
"t4"
Error of liquid refrigerant pipe (cond out) Temp (Open/short)
"T5"
Error of OIL TEMP sensor (Open/Short)
"T6"
Error of Suction temp sensor (Open/Short)
"T7"
Error of high pressure sensor (Open/Short)
"T8"
Error of low pressure sensor (Open/Short)
"T9"
Error of fixed compressor discharge sensor (Open/Short)
"E1"
System down due to the communication error after completion of tracking
"E2"
Mismatching of the numbers of set indoor units to actual indoor units
"E3"
Indoor Unit float switch error
"E5"
Setting error of option switch in indoor unit
"Ax"
Indoor Unit EVAP IN sensor breakaway
"bx"
Indoor Unit EVAP Out Sensor breakaway
"Cx"
Electronic expansion valve open error
"Dx"
Electronic expansion valve close error
"fx"
Simultaneous breakaway of indoor unit EVAP IN and EVAP OUT sensor
"G2"
Total Leakage of Refrigerant in outdoor unit/Loading Failure
"G3"
Breakaway of COND MID sensor in outdoor unit
"G6"
Breakaway of OIL temperature sensor (Detected once or more times)
"G7"
Breakaway of suction sensor
"GC"
Breakaway of load compressor discharge sensor
"9x"
OPEN/SHORT error of room sensor in indoor unit
"rx"
OPEN/SHORT of EVAP IN sensor in indoor unit
"yx"
OPEN/SHORT of EVAP OUT sensor in indoor unit
"ux"
Error of fan setting
"you"
Outdoor temperature being below -5 Deg. C when cooling mode
"to"
Outdoor temperature being over 30 Deg. C when in heating mode
E101
Communication Error between the indoor unit and the Panel
E121
Indoor unit room temp. sensor open/short Error
E122
Indoor Unit EVAP IN sensor open/short error
E123
Indoor Unit EVAP OUT sensor open/short error
E128
Indoor Unit EVAP In sensor breakaway
E129
Indoor Unit EVAP Out sensor breakaway
E130
Simultaneous breakaway of indoor unit EVAP IN/OUT Sensor
E131
Auxiliary (electric) heater sensor 1 error
E132
Auxiliary (electric) heater sensor 2 error
E133
Auxiliary (electric) heater sensor 3 error
E134
Shutter sensor error
E135
Perfect fan sensor Error
E140
MCU temp. sensor open/short
E151
Indoor unit EEV open failure
E152
Indoor unit EEV close failure
E153
Indoor unit float S/W detection
E154
Indoor fan error
E161
Mixed Operation error (operate heat & cool mode at same time)
E162
EPROM Error
E163
Option setting error
E165
Electric heater discharge temperature protect error
E166
No fan error related to the electric heater
E167
S/W setup error in peripheral control device using option
E180
The 1st MCU SOL V/V cooling heating opening at the same time
E181
The 2nd MCU SOL V/V cooling heating opening at the same time
E182
The 2nd MCU SOL V/V error
E190
There is no change of EVAP in temperature during the piping check
E191
There is no change of EVAP OUT temperature during the piping check
E192
EVAP IN temperature error during the piping check
E193
EVAP OUT temperature error during the piping check
E201
Installed indoor unit number setting error
E202
Communication Error between indoor and outdoor unit
E203
Outdoor PCB micom communication error between main and sub
E210
Communication error between the outdoor unit and MCU
E211
Indoor unit connected with confluence kit without continuity
E212
Confluence kit and setting address error
E213
MCU Address do not match with the indoor unit address
E214
Installed MCU quantity set-up error in the outdoor PCB
E215
Indoor unit address in MCU error
E216
DIP switch for indoor unit setting in MCU set ON error
E217
Dip switch for indoor unit setting in MC set OFF error
E221
OUT-TEMP sensor OPEN/SHORT sensor error
E226
Out-Temp sensor breakaway
E231
COND-OUT MAIN TEMP sensor error OPEN/SHORT
E236
COND-OUT MAIN TEMP sensor error OPEN/SHORT
E241
COND-MID sensor breakaway of outdoor unit
E246
COND-OUT 1 breakaway
E251
PWM DISCHARGE TEMP sensor error OPEN/SHORT
E256
Fixed capacity compressor 1 DCHRG sensor error OPEN/SHORT
E257
Fixed capacity compressor 2 DCHRG sensor error OPEN/SHORT
E258
Fixed capacity compressor 3 DCHRG sensor error OPEN/SHORT
E261
Digital discharge sensor breakaway
E262
Fixed 1 discharge sensor breakaway
E263
Fixed 2 discharge sensor breakaway
E264
Fixed 3 discharge sensor breakaway
E265
Sump-main breakaway error
E266
Sump Sub 1 breakaway error
E267
Sump Sub 2 breakaway error
E268
Sump Sub 3 breakaway error
E269
Suction breakaway error
E271
SUMP TEMP DIGITAL sensor error OPEN/SHORT
E276
SUMP TEMP FIXED 1 sensor error OPEN/SHORT
E277
SUMP TEMP FIXED 2 sensor error OPEN/SHORT
E278
SUMP TEMP FIXED 3 sensor error OPEN/SHORT
E291
High pressure sensor error OPEN/SHORT
E296
Low pressure sensor error OPEN/SHORT
E301
High Pressure Sensor Breakaway
E306
Low Pressure Sensor Breakaway
E308
Suction Temp. Sensor ERROR (OPEN/SHORT)
E312
Main Cooling sol. v/v open error
E313
4-Way v/v operation error
E401
Outdoor unit freezing detection 1
E402
Outdoor unit freezing detection 2
E403
Outdoor unit freezing detection 3 - freezing COMP DOWN
E404
Outdoor unit overload 1 protection control error
E405
Outdoor unit overload 2 protection control error
E406
Outdoor unit overload 3 protection control error
E407
Compressor down by high pressire sensor protection control 1
E408
Compressor down by high pressire sensor protection control 2
E409
Compressor down by high pressire sensor protection control 3
E410
Compressor down by low pressure sensor protection control 1
E411
Compressor down by low pressure sensor protection control 2
E412
Compressor down by low pressure sensor protection control 3
E413
Outdoor unit SUMP DOWN 1 protection control
E414
Outdoor unit SUMP DOWN 2 protection control
E415
Outdoor unit SUMP DOWN 3 protection control
E416
Outdoor unit discharge temperature 1 protection control
E417
Outdoor unit discharge temperature 2 protection control
E418
Outdoor unit discharge temperature 3 protection control
E419
Outdoor unit EEV open 1 self diagnosis error
E420
Outdoor unit EEV open 2 self diagnosis error
E421
Outdoor unit EEV open 3 self diagnosis error
E422
Outdoor unit EEV close 1 self diagnosis error
E423
Outdoor unit EEV close 2 self diagnosis error
E424
Outdoor unit EEV close 3 self diagnosis error
E425
Outdoor unit reverse phase detection 1 error
E426
Outdoor unit reverse phase detection 2 error
E427
Outdoor unit reverse phase detection 3 error
E428
Outdoor unit compression rate 1 error
E429
Outdoor unit compression rate 2 error
E430
Outdoor unit compression rate 3 error
E440
Forbid heating mode operation when outdoor temperature over 30 Deg. C
E441
Forbid cooling mode operation when outdoor temperature below -5 Deg. C
E442
Refrigerant charding error in the heating mode
E452
Instant Power off (dissapear when compresson run)
E551
Defrosting operation
E552
Low Discharge Pressure
E553
Eqability Operation
E554
Loading Failure Full leakage of refrigerant of outdoor unit
E601
Communication error between wired remote controller and indoor unit
E602
Communication error between master and slave wired remote controller
E603
Communication error between 7 day scheduler and wired remote controller
E701
Float S/W detection error
E702
Indoor unit EEV closing error
E703
Indoor unit EEV opening error
E704
MCU Sol v/v failure